Electrical Power Tray Cables
Type and designation
Type |
designation |
TC |
Electrical Power and Cool Tray Cables |
Deion of the pure
Power TC Cable is used to supply power to motors, or for connection to other power devices in industrial settings.
Power TC Cable is listed for direct burial and for use in Class 1, Division 2 hazardous locations and Class 1 cool circuits. This cable may be used at temperatures not to exceed75°Cin wet locations and90°Cin dry locations.
Standard
UL 83, UL 1277, UL 1581
Specification and Construction
Type TC-Power Cable Three THHN or THWN Conductors With Ground
Size (AWG or kcmil) |
Stranding |
Ground Conductor Size (AWG) |
Jacket Thickness (inches) |
A vg. Overall Diameter |
Approximate Weight |
Ampacity |
|||
inches |
mm |
lbs./1000' |
kg./km. |
75°C |
90°C |
||||
8 |
7 |
10 |
0.06 |
0.60 |
15.27 |
302 |
450 |
50 |
55 |
6 |
7 |
8 |
0.06 |
0.69 |
17.52 |
436 |
651 |
65 |
75 |
4 |
7 |
8 |
0.06 |
0.82 |
20.77 |
630 |
941 |
85 |
95 |
2 |
7 |
6 |
0.08 |
0.99 |
25.21 |
971 |
1449 |
115 |
130 |
1 |
19 |
6 |
0.08 |
1.11 |
28.16 |
1203 |
1795 |
130 |
150 |
1/0 |
19 |
6 |
0.08 |
1.18 |
29.98 |
1428 |
2131 |
150 |
170 |
2/0 |
19 |
6 |
0.08 |
1.26 |
32.07 |
1714 |
2558 |
175 |
195 |
3/0 |
19 |
4 |
0.08 |
1.39 |
35.24 |
2145 |
3202 |
200 |
225 |
4/0 |
19 |
4 |
0.08 |
1.49 |
37.87 |
2591 |
3867 |
230 |
260 |
250 |
37 |
4 |
0.11 |
1.68 |
42.72 |
3150 |
4701 |
255 |
290 |
350 |
37 |
3 |
0.11 |
1.89 |
47.99 |
4215 |
6291 |
310 |
350 |
500 |
37 |
2 |
0.11 |
2.15 |
54.57 |
5782 |
8630 |
380 |
430 |
750 |
61 |
1 |
0.11 |
2.63 |
66.74 |
8652 |
12914 |
475 |
535 |
Note: Ampacities are based on Table 310.16 of the NEC, 2002 Editon. Ampacities are for general use with a90°Cconductor and300Cambient temperature asspecified in section 310.15 and in cable trays as specified in section 392-11.